Effect of flanges on the velocity in front of exhaust ventilation hoods
Contenido multimedia no disponible por derechos de autor o por acceso restringido. Contacte con la institución para más información.
Tag | 1 | 2 | Valor |
---|---|---|---|
LDR | 00000nab a2200000 i 4500 | ||
001 | MAP20071017217 | ||
003 | MAP | ||
005 | 20080418114956.0 | ||
007 | hzruuu---uuuu | ||
008 | 940208e19781201gbr|||| | |00010|eng d | ||
035 | $a6800003121 | ||
040 | $aMAP$bspa | ||
084 | $a872 | ||
100 | 1 | $0MAPA20080043179$aFletcher, B. | |
245 | 1 | 0 | $aEffect of flanges on the velocity in front of exhaust ventilation hoods$cB. Fletcher |
520 | $aThe adittion of a flange to a local exhaust ventilation hood can produce a large increase in velocity in front of the hood. It is shown that an optimum flange width exists beyond which there is little further increase in velocity. As hood aspect ratio increases, the effect of flanges increases and the addition of even small flanges to slots can have an appreciables effect. Velocity increases of over 55% have been measured in front of hoods of aspect ratio 16:1 | ||
650 | 1 | 1 | $0MAPA20080585679$aHigiene industrial |
650 | 1 | 1 | $0MAPA20080605278$aContaminantes químicos |
650 | 1 | 1 | $0MAPA20080616441$aContaminación atmosférica |
650 | 1 | 1 | $0MAPA20080539566$aPolvo |
650 | 1 | 1 | $0MAPA20080552923$aVelocidad |
650 | 1 | 1 | $0MAPA20080537210$aAire |
650 | 1 | 1 | $0MAPA20080560997$aVentilación |
650 | 1 | 1 | $0MAPA20080612597$aSistemas de ventilación |
740 | 4 | $aThe Annals of occupational hygiene | |
773 | 0 | $tThe Annals of occupational hygiene$dOxford [etc.]$gnº 3, December 1978 ; p. 265-269 |